Setting Features (cont'd)
If the programmed Setting Logic results in none of the selected groups being allowed to set, a warning
message is displayed on the keypad. This message does not appear if at least one group sets.
Entry Time
The system begins the unsetting routine whenever a Final or Entry zone activates. The Entry/Exit Horns
pulse slowly indicating that the entry time countdown has started. The user must go directly to the keypad,
using the agreed entry route, and unset the system before the entry time expires. When 75% of the entry time
has elapsed the Entry/Exit horns pulse rapidly, indicating that time is running short.
Timeout (Slow Entry)
If the entry time expires before a valid code is entered to unset the group, a full alarm occurs. This is recorded
in the event log as a Timeout against the group which was in the process of being unset.
Straying from the Entry Route
If, during the entry routine, the user strays from the agreed entry route and activates a zone in a protected
area, a full alarm occurs.
Abort Time
Should the user exceed the entry time or stray from the entry route a full alarm occurs. However the activation
of the intruder output can be delayed to allow time for the user to abort the remote signalling.
The Abort Time parameter can also be programmed so that an Intruder alarm is activated immediately the
entry time expires or a zone is activated, but entry of any valid code cancels the alarm and deactivates the
Intruder outputs without the need for a system reset.
Abort Setting Message
Zones that are open or opened during the exit period are indicated to the user by a rapid audible tone from the
entry/exit horns. The keypad displays the open zones and then prompts the user to abort the setting by press-
ing the ESC key. This message is designed to prevent users from re-entering the building, closing the open
zones, allowing the system to set and trapping the user in the building.
Fail to Set
An output type (Option 53-Program output 40, Fail Set) is available that activates if a full set has not
occurred after a programmed period of time (determined by Option 51-Parameter 35, Fail to Set) from the
start of the setting procedure.
Power Failure While System is Set
When power is restored to the system, following a complete mains (a.c.) and standby battery (d.c.) power
failure, the system attempts to return to the set status — full or part — prior to the power failure. The system
begins the setting procedure. If there are no zones open that prevent the system from setting, at the end of the
programmed exit time, the appropriate groups and parts are set.
2 Groups not set
2 Groups not set
2 Groups not set
2 Groups not set
2 Groups not set
[<],[>]
[<],[>]
to view
to view
[<],[>]
[<],[>]
[<],[>]
to view
to view
to view
6-10
Galaxy Dimension Installer Manual