69 - Access Control (cont'd)
2 = Relay Duration
This is the period, following the user card swipe, that the MAX relay is activated allowing a door strike to be
unlocked and the door to be opened without creating an alarm. The MAX relay de-activates as soon as the
door contact opens or the Open Timeout occurs.
On entering the Relay Duration parameter, the current value is displayed; assign the required time within the
range 01 – 60 seconds, the default time is 5 seconds. Press the ent key to save the programming and return
to the previous menu level.
NOTE: Pressing the A key increases the time by one second increments, the B key decreases the time in one
second decrements.
3 = Open Timeout
This is the period following the user card swipe that the door can remain open when gaining access. If the
door remains open longer than the period assigned to the Open Timeout, then an alarm occurs.
NOTE: If the Open Timeout is programmed as 0 seconds, then the door can remain open indefinitely
without resulting in an alarm being activated.
On entering the Open Timeout parameter, the current value is displayed; assign the required time within the
range 00 – 60 seconds, the default time is 10 seconds. Press the ent key to save the programming and return
to the previous menu level.
NOTE: Pressing the A key increases the time by one second increments, the B key decreases the time in one
second decrements.
4 = Group Config
1=Alarm Group
On selecting the Alarm Group option, the group currently allocated to the MAX is displayed. Pressing
the group number toggles the group assigned to the MAX. The MAX does not allow access through
the door when the group is set. A user must have this group assigned to them in order to gain access at
this door.
Multi-group Systems
The larger galaxy panels have 32 groups; these are displayed on the MAX in block of 8 groups, sub-divided
into A, B, C and D. Use the A or B key to move between the group blocks; press keys 1 – 8 to assign the
relevant groups in each block to the MAX.
When the required groups have been assigned to the user, press the ent key to accept the programming and
return to the previous menu level.
Galaxy Dimension Installer Manual
6-182