56 - Communications (cont'd)
56.1.02 Telephone No. 1
Telephone number 1 must be entered. This is the main telephone number that the alarms are signalled to. Up
to 22 digits may be entered, including control modifiers. The control modifiers are entered using the
keys:
Pause (for two seconds before dialling the next digit). Multiple entries can be made, for example,
entering
gives a six second pause.
#
Dial tone detect (wait for new dial tone). Each dial tone detect lasts for 15 seconds. Multiple entries can
be made, for example, entering ## gives a 30 second dial tone detect. If a new dial tone is not detected in this
time, then the dialling attempt is aborted. This is counted as a fail to communicate.
The B key is used to erase an existing telephone number. Each press deletes the last digit displayed.
56.1.03 Account No.
This is the site identifier. A unique account number must be entered, this can be up to a maximum of six digits
although four digits is the standard.
The B key is used to erase an existing number. Each press deletes the last digit displayed.
NOTE: Entering the account number into this menu option automatically copies the number to all channel or
group triggers in the selected format. Any individual account numbers that have been programmed
are overwritten.
56.1.04 Receiver
The transmission destination can be set to one of three modes:
1 = Single
Reports to the telephone number programmed in Telephone Number 1.
2 = Dual
Reports to both numbers programmed in Telephone Number 1 and Telephone Number 2. The alarm must
be transmitted to both numbers.
3 = Alternate
Reports to Telephone Number 1 OR Telephone Number 2. Each number is tried in sequence until the
alarm is successfully transmitted. The alarm is only transmitted to one number. Telephone number 1 is always
the first number attempted.
56.1.05 Telephone No. 2
A second telephone number is available to support Dual and Alternate dialling to a second destination
receiver. The programming is identical to Telephone Number 1.
The B key is used to erase an existing number. Each press deletes the last digit displayed.