Mitsubishi Electric MELSERVO-J3 Series Manual page 437

Hide thumbs Also See for MELSERVO-J3 Series:
Table of Contents

Advertisement

Part 7: Review on Replacement of Optional Peripheral Equipment
(1) Wires for power supply wiring
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
In this case, the power supply wire used is a 600 V plastic one and the wiring distance is 30 m or less.
When the wiring distance exceeds 30 m, select another wire size in consideration of the voltage drop.
The alphabet letters (a/b/c) on the table correspond to crimp terminals used when wiring a servo
amplifier.
The method of wiring a servo motor differs depending on the type and capacity of the servo motor.
To comply with the UL/cUL (CSA) standard, use UL-approved copper wires rated at 60˚C or higher for
wiring.
2) Control power supply lead
8) Power regenerative
Note
There is no L
POINT
Use 600 V Grade heat-resistant polyvinyl chloride insulated wires (HIV wires) for
HF-JP series servo motor.
1) Main circuit power supply lead
Power supply
converter lead
Power regenerative
converter
Regenerative option
for 1-phase 100 to 120 V AC power supply.
3
Servo amplifier
L
U
1
L
V
2
L
(Note)
W
3
L
11
L
21
N
C
P
C
P
4) Regenerative option lead
7 - 14
3) Motor power supply lead
4) Electromagnetic
5)
brake lead
Encoder cable
Power supply
6) Cooling fan lead
7) Thermal
Servo motor
U
V
Motor
W
Electro-
B1
magnetic
B2
brake
Encoder
Cooling fan
BU
BV
BW
Thermal
OHS1
OHS2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents