Chapter5 Utility Package (Gx Configurator-Ti); Utility Package Functions - Mitsubishi MELSEC-Q Series User Manual

Channel isolated thermocouple input module, gx-configurator-ti sw1d5c-qtiu-e, programmable controller
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

5
UTILITY PACKAGE (GX Configurator-TI)
CHAPTER5
5.1

Utility Package Functions

Table 5.1 shows a list of the utility package functions.
Function
(1)
Make initial setting for operating the Q68TD-G-H01 channel-by-channel.
Set the values of the items which require initial setting.
•Conversion enable/disable setting
•Averaging processing selection
•Time/count/moving average/time constant setting
•Warning output enable/disable setting (Process alarm)
•Thermocouple type
Initial
•Process alarm lower lower limit value
setting
•Process alarm lower upper limit value
•Process alarm upper lower limit value
•Process alarm upper upper limit value
•Warning output enable/disable setting (Rate alarm)
(2)
The data for which initial setting has been completed is registered in the parameters for the programmable
controller CPU, and automatically written to the Q68TD-G-H01 when the programmable controller CPU
changes to the RUN status.
(1)
Set the automatically refreshed Q68TD-G-H01 buffer memory channel-by-channel.
•Conversion completion flag
Automatic
•CH
Measured temperature value
refresh
•Error code
setting
(2)
The values stored in the Q68TD-G-H01 buffer memory where automatic refresh setting was made are
automatically read or writhen when the END instruction of the programmable controller CPU is executed.
Monitors and tests the buffer memory and I/O signals for the Q68TD-G-H01.
•Module ready
•Operating condition setting completion flag
•Operating condition setting request
•Offset/gain setting mode status flag
•User range write request
•Channel change completion flag
(1)
CH
Monitor/test
•Conversion enable/disable setting
•Averaging processing selection
•Time/count/moving average/time constant setting
Monitor/
•Conversion completion flag
test
•Measured temperature value
•Error code
•Thermocouple type
•Warning output enable/disable setting (Process alarm) •Scaling value
•Warning output flag (Process alarm) lower limit value
•Warning output flag (Process alarm) upper limit value •Scaling range lower limit value
•Process alarm lower lower limit value
•Process alarm lower upper limit value
•Process alarm upper lower limit value
•Process alarm upper upper limit value
5
- 1
5.1 Utility Package Functions
UTILITY PACKAGE (GX Configurator-TI)
Table 5.1 Utility Package (GX Configurator-TI) Function List (1/2)
Description
•Rate alarm warning detection period
•Rate alarm upper limit value
•Rate alarm lower limit value
•Scaling range lower limit value
•Scaling range upper limit value
•Scaling valid/invalid setting
•Scaling width lower limit value
•Scaling width upper limit value
•Disconnection state conversion setting
•Conversion setting for disconnection state value
•Setting range
•Warning output flag
•Disconnection state monitor flag
•CH
Scaling value
•Channel change request
•Disconnection state monitor signal
•Warning output signal
•Conversion completion flag
•Error flag
•Error clear request
•Warning output enable/disable setting (Rate alarm)
•Rate alarm warning detection period
•Warning output flag (Rate alarm) lower limit value
•Warning output flag (Rate alarm) upper limit value
•Rate alarm upper limit value
•Rate alarm lower limit value
•Disconnection state monitor flag
•Scaling valid/invalid setting
•Scaling range upper limit value
•Scaling width lower limit value
•Scaling width upper limit value
•Disconnection state conversion setting
•Conversion setting for disconnection state value
Reference
section
Section 5.4
Section 5.5
Section 5.6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q68td-g-h01