Disconnection state conversion setting (Un\G164, Un\G165)

(1) Select the value to be stored in the CH
(Un\G11 to Un\G18) when disconnection state is confirmed.
(2) When "Up scale"(0
measured temperature range + 5% of the measured temperature range)
of the currently set range is stored in the CH
value (Un\G11 to Un\G18).
(3) When "Down scale" (1
of the measured temperature range - 5% of the measured temperature
range) of the currently set range is stored in the CH
temperature value (Un\G11 to Un\G18).
(4) When "Given value"(2
conversion setting for disconnection state value (Un\G166 to Un\G173)
is stored in the CH
(5) The default value is set to "Down scale".
Un\G164 (Disconnection state
conversion setting CH1 to CH4)
Un\G165 (Disconnection state
conversion setting CH5 to CH8)
(6) To activate the setting, turning ON/OFF the operating condition setting
request (Y9) is required.
(7) For details of disconnection state conversion setting, refer to Section
3.2.2.
) is selected, upscale (the maximum value of the
H
) is selected, "Down scale" (the minimum value
H
) is selected, the setting value of the CH
H
measured temperature value (Un\G11 to Un\G18).
to
b15
b12 b11
CH4
CH8
3.4.23 Disconnection state conversion setting (Un\G164, Un\G165)
measured temperature value
measured temperature
to
b8 b7
to
CH3
CH2
CH7
CH6
Measured temperature value when
confirming disconnection state
Up scale
Down scale
Given value
3.4 Buffer Memory
measured
to
b4 b3
b0
CH1
CH5
Setting
value
0
H
1
H
2
H
3
- 46
1
2
3
4
5
6
7
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q68td-g-h01

Table of Contents