SPECIFICATIONS
(3) Offset/gain setting mode status flag (XA)
3
- 19
3.3 I/O Signals Transferred to/from Programmable Controller CPU

3.3.2 I/O signal details

(c) The operating condition setting completion flag (X9) turns OFF in the following
status.
• When the operating condition setting request (Y9) is ON.
Module ready (X0)
Operating condition
setting completion flag (X9)
Operating condition setting
request (Y9)
Conversion enable/disable
setting (Un\G0)
Conversion completion
flag (XE)
(a) In offset/gain setting mode
1) This signal is used as an interlock condition to turn ON/OFF the user range
write request (YA) when the value at completion of offset/gain setting
adjustment is registered.
2) See Section 4.6 regarding the offset/gain settings.
Module ready (X0)
Offset/gain setting mode
status flag (XA)
User range write request (YA)
(b) In normal mode
1) This signal is used as an interlock condition to turn ON/OFF the user range
write request (YA) when the user range is restored.
2) Refer to CHAPTER 7 for the user range restoration.
Module ready (X0)
Offset/gain setting mode status
flag (XA)
User range write request (YA)
Executes in Q68TD-G-H01
Executes in sequence program
Conversion
Conversion enabled
disabled
Executes in Q68TD-G-H01
Executes in sequence program
OFF
Executes in Q68TD-G-H01
Executes in sequence program
ON