Time/Count/Moving Average/Time Constant Setting (Un\G1 To Un\G8) - Mitsubishi MELSEC-Q Series User Manual

Channel isolated thermocouple input module, gx-configurator-ti sw1d5c-qtiu-e, programmable controller
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.3
CH[ ]
Un\G8)
(1) Set the time, count, moving average, or time constant for primary delay
filter for each channel that is specified for averaging processing.
(2) The default value is set to 0000
(3) To activate the setting, turning ON/OFF the operating condition setting
request (Y9) is required.
(4) Settable range is shown below.
POINT
3.4.3 CH[] time/count/moving average/time constant setting (Un\G1 to Un\G8)
time/count/moving average/time constant setting (Un\G1 to
Table 3.9 Settable range
Processing method
Time average
Count average
Moving average
Primary delay filter
* 1 : The values can be set in units of 1ms; however, the processing is carried out in units of 320ms.
When a value out of the above setting range is written to a channel, an error (error
code 20 , 30 , 31 , 32 ) occurs on the channel. Then the error flag (XF) turns
ON and the conversion processing is executed with the setting before the error
occurrence.
.
H
Setting value
*1
1280 to 5000 (ms)
4 to 500 (times)
2 to 60 (times)
*1
320 to 5000 (ms)
3.4 Buffer Memory
1
2
3
4
5
6
7
8
3
- 32