(1) The conversion completion flag turns ON(1) when conversion for the
(2) By turning ON the operating condition setting request (Y9), the flag
3.4.5
(1) The "thermal EMF value" input from the thermocouple is converted into
(2) The value of the measured temperature to the first decimal place is
(3) The default value is set to "0" for all channels.
[Example 1] At the measured temperature value of 123.025
[Example 2] At the measured temperature value of -123.025
3
- 33
3.4 Buffer Memory

3.4.4 Conversion completion flag (Un\G10)

Conversion completion flag (Un\G10)
conversion-enabled channel is completed.
For averaging processing, the flag turns ON(1) after the first averaged
value is stored into the CH
Un\G18).
The conversion completion flag (XE) turns ON when conversion for
every conversion-enabled channel is completed.
returns to the default value of OFF(0) and it turns ON(1) after conversion
is completed.
b15 b14 b13 b12 b11 b10
0
0
0
0
0
Data for b8 to b15 are fixed to "0".
CH[ ]

measured temperature value (Un\G11 to Un\G18)

a "temperature value" to detect a temperature.
multiplied by 10 and the result is stored into buffer memory in 16-bit
signed binary. (The second decimal place and on are rounded down.)
b15 b14 b13 b12 b11 b10
0
0
0
0
0
b15 b14 b13
b12 b11 b10
1
1
1
1
1
measured temperature value (Un\G11 to
b9
b8
b7
b6
0
0
0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
b9
b8
b7
b6
1
0
0
1
1
b9
b8
b7
b6
0
1
1
0
0
b5
b4
b3
b2
b1
0: During conversion or unused
1: Conversion completed
..... 1230 is stored.
b5
b4
b3
b2
b1
0
0
1
1
1
..... -1230 is stored.
b5
b4
b3
b2
b1
1
1
0
0
1
b0
b0
0
b0
0