UTILITY PACKAGE (GX Configurator-TI)
5.6.3
Perform operation in the following sequence to save/restore the user range.
(1) Switch to the OMC refresh data screen
(2) User range saving
(3) User range restoration
5
- 23
5.6 Monitoring/Test

5.6.3 OMC (Online Module Change) refresh data

OMC (Online Module Change) refresh data
Perform the operation in Section 5.6.1 to display the OMC refresh data screen.
(a) Change the Setting value field of Online Module Change read request to
"Request", and click the
When read is completed, the values are displayed in the Current value fields of
CH
Factory default offset/gain value/User range settings offset/gain value/User
range settings offset/gain thermal EMF value.
(b) Compare the values with those in the range reference table, and take a note of the
values if they are correct.
Refer to Section 7.4 for the range reference table.
(a) Set the noted values into the Setting value fields of CH
gain value/User range settings offset/gain value/User range settings thermal EMF
offset/gain value.
(b) Select all the Setting value fields of CH
User range settings offset/gain value/User range settings thermal EMF offset/gain
value, and click the
When write is completed, the set values are displayed in the Current value fields
of them.
(c) Change the Setting value field of online module change write request to
"Request", and click the
Make sure that the indication in the Current value field of online module change
write request changes from "Request" to "OFF" on completion of write.
button.
Factory default offset/gain input value/
button.
button.
Factory default offset/