Functions Available By Use Of Software; For Cc-Link; Functions Available By Use Of Gx Configurator-St - Mitsubishi MELESEC-ST User Manual

Table of Contents

Advertisement

9 FUNCTIONS AVAILABLE BY USE OF SOFTWARE

9 FUNCTIONS AVAILABLE BY USE OF SOFTWARE

9.1 For CC-Link

9.1.1 Functions available by use of GX Configurator-ST

Function
Information monitoring
Status monitoring
I/O data monitoring function
Online module change
Forced output test function
Input response time setting
function
Setting of output status
(CLEAR/HOLD) at module
error
Power supply capacity check
function
9
1) Operate with GXConfigurator-ST.
2) Execute a command from the master station to perform operation.
3) Use the button or switch of the head module to perform operation.
1: For the operation of GX Configurator-ST, refer to the GX Configurator-ST Operating Manual.
2: For details, refer to the MELSEC-ST CC-Link Head Module User's Manual.
9 - 1
This chapter introduces the functions available by use of the GX Configurator-ST
connected to a head module. This manual explains power distribution modules and I/O
modules. For a head module and intelligent function modules, refer to the manuals of
the corresponding modules.
Various information on the head module and slice modules can
be monitored.
The operating status of each slice module and error history of the
head module can be monitored.
Data of Br Bit input area, Bw Bit output area, Wr Word input
area, and Ww Word output area can be monitored.
I/O modules and intelligent function modules can be replaced
while the external power supply is on. However, a power
distribution module cannot be replaced.
Slice module data in Bw.n Bit output area and Ww.n Word
output area can be forcibly output.
Setting of input response time (0.5ms/1.5ms) can be monitored.
Output module status (CLEAR/HOLD) setting can be
monitored.
CLEAR: Output is forcibly turned off when a module
becomes faulty.
HOLD: Output is held in the status as when a module
becomes faulty.
Judges whether the 5VDC maximum rated output current of the
power distribution module is sufficient for the total 5VDC internal
current consumption of the slice modules.
Description
MELSEC-ST
Operation
Reference
method
section
1) 2) 3)
1
2
1
2
1
This
section (1)
This
section (2)
1
: Applicable,
: N/A
9 - 1