Disconnection state conversion setting (Un\G164, Un\G165)
(Q68TD-G-H01only)
When disconnection state is checked, a value stored into CH
value (Un\G11toUn\G18) is set. (Refer to Section 3.2.3)
The value to be stored is selected from "Up scale", "Down scale" or "Given value".
(1) Setting methods
(a) Set the value to be stored in buffer memory.
Un\G164 (Disconnection state
conversion setting CH1 to CH4)
Un\G165 (Disconnection state
conversion setting CH5 to CH8)
Figure 3.39 Setting of Disconnection state conversion setting (Un\G164, Un\G165)
(b) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to "Down scale" (1111
POINT

3.4.26 Disconnection state conversion setting (Un\G164, Un\G165) (Q68TD-G-H01only)

b15
to
b12 b11
CH4
CH8
The value to be stored into CH
in the disconnection state check changes as follows, depending on the setting
value.
1) Up scale (0
)
H
Up-scale of the range currently set is stored.
2) Down scale (1
)
H
Down-scale of the range currently set is stored.
3) Given value (2
)
H
The value set in CH
(Un\G166toUn\G173) is stored.
If a value out of the setting range is set, the module operates with the default
setting, "Down scale"(1
).
H
to
b8 b7
CH3
CH2
CH7
CH6
Measured temperature value when
confirming disconnection state
Up scale
Down scale
Given value
Measured temperature value (Un\G11toUn\G18)
Conversion setting for disconnection state value
).
H
3.4 Buffer Memory
Measured temperature
to
b4 b3
to
CH1
CH5
Setting
value
0
H
1
H
2
H
3
- 57