Time Table And Settings For Program Sequence Pme71.401 - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

10.3 Time table and settings for program sequence PME71.401...

Type
TSA
PME71.401...
tw
max.
Requirements
2.5
3
Factory setting
---
t3n+0.45
Max.
2.5
14
Min.
---
---
Step size
---
---
Function parameter
Repetition in the event of loss of flame during operation
<2: None
= 2: 1 x
Legend
tw
Waiting time
TSA
Safety time
t1
Prepurge time
t3
Preignition time
1)
Response time to a change of signal by the air pressure switch (opens) and response time in the event of loss of flame
2)
Response time to a change of signal by the inputs (e.g. pressure switch-min)
3)
Flame detection time
Building Technologies Division
Infrastructure & Cities Sector
Times in seconds
t1
t3
t3n
P225
P226
P257
min.
min.
approx.
30
2
2.5
29.106+2.1
2.058
2.205+0.3
1237+2.1
37.485
13.23+0.3
0+2.1
1.029
0+0.3
4.851
0.147
0.147
Parameter number
Basic Documentation LME7...
10 PME71.401...
t4
t8
t10
P230
P234
P224
1)
2)
min.
min.
approx.
8
0
15
---
---
8.232
0
13.818
---
---
74.97
1237
13.818
1
0.45
3.234
0
0
0.3
0.3
0.294
4.851
0.254
---
---
Factory setting
P240
0
t3n
Postignition time (P257 +0.3 seconds)
t4
Interval: End of safety time – load controller release
t8
Postpurge time
t10
Specified time air pressure switch state message (timeout)
3)
---
---
0.45
---
---
51/245
CC1P7105de
29.11.2011