Install Coupled Bonding Conductor
For a high-rise building, connect the CBC to an approved building ground on each floor. To
provide the coupled bonding protection:
1
Connect one end of the conductor to a telephone cable building entrance protector
ground that is connected to an approved ground.
2
Route the conductor next to the exposed telephone cables being protected until it reaches
the crossconnect nearest to the telephone system.
3
Position the nonexposed telephone cables at least 12 inches (30.5 centimeters) away
from exposed telephone cables whenever possible.
Terminate the other end to the single-point ground block provided for the telephone
4
system.