Siemens WL Series Operating Instructions Manual page 346

Low voltage insulated case circuit breaker
Table of Contents

Advertisement

Function Overview of the Electronic Trip Units
Basic Functions
Long-time overcurrent protection
Function can be switched ON/OFF
Setting range I R = I n x ...
Switch-selectable overload protection
I n
( I 2 t or I 4 t dependent function)
L
Setting range of time delay class t R at I 2 t
(seconds)
Setting range of time delay t R at I 4 t
(seconds)
Thermal memory
Phase loss sensitivity
N-conductor protection
N
Function can be switched ON/OFF
N-conductor setting range I N = I n x ...
Short-time delayed overcurrent protection
Function can be switched ON/OFF
Setting range I sd = I n x ...
Setting range of time delay t sd , fixed
(seconds)
S
Switch-selectable short-time delay
short-circuit protection
( I 2 t dependent function)
Setting range of time delay t sd at I 2 t
(seconds)
Zone Selective Interlocking (ZSI) function
Instantaneous overcurrent protection
Function can be switched on/off,
Extended Instantaneous Protection
I
is enabled when OFF
Setting range I i = I n x ...
Ground fault protection
Trip and alarm function
Detection of the ground fault current
by residual summing method
Detection of the ground fault current
by direct summing method
Setting range of the I g for trip
G
Setting range of the I g for alarm
Setting range of the time delay t g
(seconds)
Switch-selectable
ground fault protection
( I 2 t / fixed)
Setting range time delay t g at I 2 t
ZSI ground function
1
Extended Instantaneous Protection (EIP) allows the WL breaker to be applied at the withstand rating
of the breaker with minus 0% tolerance; that means no instantaneous override whatsoever. EIP further
enables the circuit breaker to be applied up to the full instantaneous rating of the breaker on systems
where the available fault current exceeds the withstand rating.
Ground Fault Module cannot be removed after installation.
2
25 – 7
ETU725
0.4, 0.45, 0.5, 0.55,
0.6, 0.65, 0.7, 0.8,
0.9, 1
10s, fixed at 6 x I r
at t sd =20ms (M)
1.25, 1.5, 2, 2.5,
3, 4, 6, 8, 10, 12
0, 0.02 (M), 0.1,
0.2, 0.3, 0.4
– fixed only
I i = 0.8 x I cw
50kA max
2
ETU727
ETU745
0.4, 0.45, 0.5, 0.55,
0.4, 0.45, 0.5, 0.55, 0.6,
0.6, 0.65, 0.7, 0.8,
0.65, 0.7, 0.8, 0.9, 1
0.9, 1
10s, fixed at 6 x I r
2, 3.5, 5.5, 8, 10,
14, 17, 21, 25, 30
1, 2, 3, 4, 5
✔ (via slide switch)
at t sd =20ms (M)
at t sd =20ms (M)
✔ (via slide switch)
✔ (via slide switch)
1
0.5 ... 1
✔ (via rotary switch)
1.25, 1.5, 2, 2.5,
1.25, 1.5, 2, 2.5,
3, 4, 6, 8, 10, 12
3, 4, 6, 8, 10, 12
0, 0.02 (M), 0.1,
0.02 (M), 0.1, 0.2,
0.2, 0.3, 0.4
0.3, 0.4, OFF
✔ (via rotary switch)
– fixed only
0.1, 0.2, 0.3, 0.4
per CubicleBUS module
✔ (via rotary switch)
I i = 0.8 x I cw
1.5, 2.2, 3, 4, 6, 8, 10, 12
50kA max
0.8 x I
✔ (standard)
(field installable module)
O
A, B, C, D, E
A, B, C, D, E
A, B, C, D, E
0.1, 0.2, 0.3, 0.4, 0.5
0.1, 0.2, 0.3, 0.4, 0.5
0.1, 0.2, 0.3, 0.4, 0.5
per CubicleBUS module
✔ available
not available
optional
O
1
= max, OFF= I
=EIP
cw
cw