Cms-6000 Media Server Grounding - Avaya S6200 Manual

Conferencing servers, meeting exchange 4.1
Hide thumbs Also See for S6200:
Table of Contents

Advertisement

1. Unpack the power cable assembly that was shipped with your system.
2. Remove the nuts on the power terminal bolts.
3. Connect the red wire (–) to the –48 V connector.
4. Connect the black wire (GRND) to the 0 VR connector.
5. Replace the nuts and tighten using no more than 30 inch-lbs torque.
6. Repeat for the redundant power source, if desired.
7. Make sure that power for both switches A and B are OFF (O).
8. Connect the other end of the power cable to the DC power source.

CMS-6000 Media Server Grounding

The CMS-6000 Media Server has a grounding clamp and stud on the power input panel to tie
into the facility and Rack ground systems.
Connecting the CMS-6000 Media Server to Ground is extremely important. After rack-mounting
the CMS-6000 Media Server, ground it using the ground cable that was shipped with your
system, and the chassis ground clamp on the back of the CMS-6000 Media Server.
There are two kinds of ground cable. Either may have shipped with your system.
A ground cable with no connector at the CMS-6000 Media Server end of the cable. The
shelf end of the cable is stripped to expose a short length of copper wire.
A ground cable with a round crimp connector at the CMS-6000 Media Server end of the
cable.
To ground the CMS-6000 Media Server using stripped wire cable, follow these steps:
1. Unpack the ground cable that was shipped with your system.
2. Strip the cable further, if necessary, to expose approximately 1/2 inch of copper wire on the
shelf end of the cable.
Connecting the System
Issue 1 July 2006
35