1. Unpack the power cable assembly that was shipped with your system.
2. Remove the nuts on the power terminal bolts.
3. Connect the red wire (–) to the –48 V connector.
4. Connect the black wire (GRND) to the 0 VR connector.
5. Replace the nuts and tighten using no more than 30 inch-lbs torque.
6. Repeat for the redundant power source, if desired.
7. Make sure that power for both switches A and B are OFF (O).
8. Connect the other end of the power cable to the DC power source.
CMS-6000 Media Server Grounding
The CMS-6000 Media Server has a grounding clamp and stud on the power input panel to tie
into the facility and Rack ground systems.
Connecting the CMS-6000 Media Server to Ground is extremely important. After rack-mounting
the CMS-6000 Media Server, ground it using the ground cable that was shipped with your
system, and the chassis ground clamp on the back of the CMS-6000 Media Server.
There are two kinds of ground cable. Either may have shipped with your system.
A ground cable with no connector at the CMS-6000 Media Server end of the cable. The
●
shelf end of the cable is stripped to expose a short length of copper wire.
A ground cable with a round crimp connector at the CMS-6000 Media Server end of the
●
cable.
To ground the CMS-6000 Media Server using stripped wire cable, follow these steps:
1. Unpack the ground cable that was shipped with your system.
2. Strip the cable further, if necessary, to expose approximately 1/2 inch of copper wire on the
shelf end of the cable.
Connecting the System
Issue 1 July 2006
35