FXS mode: Control input
If FXS interfaces are configured as control inputs, one or more of the switch groups
can be switched between Positions 1, 2 and 3. An external switch or a relay is con-
nected for this purpose. An LED can be connected to the circuit to indicate the
switch state. The no-load voltage is 24 VDC; the current is limited to 25mA.
The permissible switch and loop resistances are as follows:
• Active state (On): < 1 k
• Passive state (Off): > 4 k
There are no special requirements for the cables.
Warning
Control inputs must have a floating connection.
Fig. 61
Connection for FXS mode: Control input
In the switch group configuration in (
inputs of a switch group. To be able to control all 3 switch positions of a switch
group, you need 2 control inputs which switch the switch position of the switch
group depending on the status.
Tab. 72
Switch group control via the control inputs
FXS control input 1
Off
On
any
Other conditions:
• The same control inputs can control one or more switch groups.
• The same switch group can only be switched by the 2 assigned control inputs.
• Control of the switch groups using the control inputs takes priority over control
using function codes.
Aastra 470 as of R3.2
syd-0337/1.6 – R3.2 – 09.2014
a
25mA
24 VDC
b
FXS interface
=xb) the ports are assigned to the control
FXS control input 2
Off
Off
On
Switch positions of the switch group
Position 1
Position 2
Position 3
Installation
149