3.3.2
Mapping
Table 3-6
With the parameter "IEC 103 Settings - Counters" (see chapter 3.3.1) the user can
select, whether the energy values (table 3-6) will be transferred.
3.3.2.1
Energy Counters from Binary Inputs
Energy Counter 1 and Energy Counter 2 count energy pulses from binary inputs via
binary input module.
For conversion of the transmitted pulses to an energy value, a factor "Energy increase
per pulse" has to be defined during parameterization of the binary input (ref. to the
SIMEAS P 7KG7750/55 Device Manual).
3.3.2.2
Energy Counters Calculated from Measurement Values
The required conversion factor for the calculation is 1837.
The following formula applies to the calculation of the energy:
Formula
Energy
U
I
nom
1 h:
1837: Conversion factor
Power Meter, SIMEAS P 7KG7750/55, Manual
E50417-B1076-C375-A3, Release 01.2009
#
Value
1
Energy counter 1
2
Energy counter 2
3
Active energy demand
4
Active energy supply
5
Reactive energy inductive
6
Reactive energy capacitve
Mapping table
×
×
Unom
Inom
=
----------------------------------------------------------------------------------------------------- -
: Voltage measuring range L-N x Transformation ratio of the voltage transformer
nom
:
Current measuring range x Transformation ratio of the current transformer
1 hour
Comment
from
binary input
from calculated mea-
surement values
×
1 h
Energycounter
1837
Data Mapping
133
55
no
205
133
56
no
205
133
51
no
205
133
53
no
205
133
52
no
205
133
54
no
205