Appendix
7.2

Allowable Piping Length

Points of piping desigh
1. b + c = 100m
2. Level difference between outdoor units (Main and Sub units) a ≤ 5 m
3. Piping distance between first branch and the farthest indoor unit ≤ 40 m
4. Level difference between indoor units ≤ 15 m
5. Level difference between indoor and outdoor unit ≤ 50 m
6. Refnet joint and header are not downstream for first installed Refnet header.
94
(Level difference is lower than 40 m when outdoor unit is installed below indoor unit.)