Selection of
When placing several units in close proximity to each other some thought should be given to the possibility
Location
of short circuiting and also to the provision of adequate space for servicing. (For more detailed information
please refer to the system design materials.)
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial
environment. If installed as a household appliance it could cause electromagnetic interference.
The VRV plus outdoor units should be installed in a location that meets the following requirements:
1. The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration
2. The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is
3. There is no danger of fire due to leakage of inflammable gas.
4. Ensure that water cannot cause any damage to the location in case it drips out the unit (e.g. in case of
5. The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping
6. Select the location of the unit in such a way that neither the discharged air nor the sound generated by
7. Make sure that the air inlet and outlet of the unit are not positioned towards the main wind direction.
Caution
1. An inverter air conditioner may cause electronic noise generated from AM broadcasting. Examine
2. In heavy snowfall areas, select an installation site where snow will not affect operation of the unit.
3. The refrigerant R-407C itself is nontoxic, nonflammable and is safe. If the refrigerant should leak
General Information
and noise generation.
available. (Refer to figure 1 and choose one of both possibilities.)
RSXYP16,18,20
≥10
≥20
≥500
Front side
≥50
≥100
Front side
H ≤ 1500
⇒ A ≥ 500
h ≤ 500
⇒ B1 ≥ 300
H = 1500+X ⇒ A ≥ 500+X/2
h = 500+Y ⇒ B1 ≥ 300+Y/2
B1
A
B2
H ≤ 1500
⇒ A ≥ 500
h ≤ 500
⇒ B2 ≥ 100
H = 1500+X ⇒ A ≥ 500+X/2
h = 500+Y ⇒ B2 ≥ 100+Y/2
a blocked drain pipe).
length. (See "Example of connection".)
the unit disturb anyone.
Frontal wind will disturb the operation of the unit. If necessary, use a windscreen to block the wind.
where to install the main air conditioner and electric wires, keeping proper distances away from stereo
equipment, personal computers, etc.
6
2
3
4
5
1
If the electric wave of AM broadcasting is particularly weak, keep distances of 3m or more and use
conduit tubes for power and transmission lines.
however, its concentration may exceed the allowable limit depending on room size. Due to this it could
be necessary to take measures against leakage. Refer to the chapter 'Caution for refrigerant leaks'.
RSXYP24,26,28,30
≥10
≥10
≥20
≥500
Front side
≥50
≥50
≥100
Front side
(mm)
Fig. 1
(V0849)
1. Personal Computer or Radio
3
2. Fuse
2
3. Earth Leak Detector
4. Remote Control
5. Cool/Heat Selector
6. Indoor Unit
Fig. 2
(mm)
(V0850)
: http://splitoff.ru/tehn-doc.html
Installation
≥10
≥50
55