Si33-003.book Page 25 Monday, June 25, 2001 9:06 AM
SiE33-003
Flange Connection
a) The flange sheet surface should be clean and undamaged. (Clean any dirt away with a cloth and check
b) Coat the flange sheet surface with refrigeration oil (Ester or ether oil) and then insert the packing. (Do
c) Tighten the bolts in opposite corners first to ensure that the connection is true.
Important points
1. Only clean refrigeration/oil should be used to coat the flange. (i.e. free from dirt or water)
2. The correct amount of torque should be applied when tightening the flange bolts.
Standard torques for tightening screws and bolts
ISO hexagonal bolt
Size
General Information
that there has been no damage.)
not use SUNISO oil.)
Class
kgf-cm ±15%
M8
125
M10
257
M12
436
M16
1,030
M20
2,050
[Example]
Order:A→C→B→D
The bolts should be tightened little by
little in the above order such that the
same degree of torque is applied
evenly to each corner.
5.8(5T)
N-m ±15%
kgf-cm ±15%
1230
302
2520
620
4280
1,050
10,100
2,480
20,100
4,950
: http://splitoff.ru/tehn-doc.html
Installation
10.9(10T)
N-m ±15%
2960
6080
10,300
24,300
48,500
25