Si33-003.book Page 84 Monday, June 25, 2001 9:06 AM
Test Operation
4.13 Centralized Control Group No. Setting
BRC1A51·52
1. When in the normal mode, push the
2. Set mode No. "00" with the
3. Push the
4. Set the group No. for each group with the
5. Push the timer
6. Push the
BRC7A Type
1. When in the normal mode, push
2. Set mode No. "00" with
3. Set the group No. for each group with
4. Enter the selected group numbers by pushing
5. Push
BRC7A Type
84
If carrying out centralized control by central remote control or unified ON/OFF control, group No. must
be set for each group individually by remote control.
Group No. setting by remote control for centralized control
the "field setting mode."
button. ∗
button to inspect the group No. display.
1-01, ...,1-15, 2-00,...4-15. However, the unified ON/OFF control displays only the group No. within
the range selected by the switch for setting each address.)
button to define the selected group No.
button to return to the normal mode.
Even if not using a remote control, connect the remote control when setting the group No., set the group
No. for centralized control, and disconnect after making the setting.
Set the group No. after turning on the power supply for the central remote control, unified ON/OFF
control, and indoor unit.
Group No. setting by infrared remote control for centralized control
"field set mode."
button.
button and return to the normal mode.
button for 4 seconds or more, and operation then enters
button (The group No. increases in the manner of 1-00,
button for 4 seconds or more, and operation then enters the
button (advance/backward).
button.
: http://splitoff.ru/tehn-doc.html
SiE33-003
General Information