(PRECAUTIONS FOR DRAIN RAISING PIPING)
Note:
General Information
To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.
Use the attached drain hose
and clamp metal
Insert the drain hose into the drain socket, up to the white tape. Tighten the clamp until the screw head
is less than 4 mm from the hose.
Wrap the attached sealing pad over the clamp and drain hose to insulate.
Insulate the drain hose inside the building.
Install the drain raising pipes at a height of less than 530 mm.
Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit.
The incline of attached drain hose
stand additional force.
If converging multiple drain pipes, install according to the procedure shown below.
Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
.
should be 75 mm or less so that the drain socket dose not have to