Si33-003.book Page 64 Monday, June 25, 2001 9:06 AM
Test Operation
4.4.2
Setting Mode 2
To switch from setting mode 1 (normal) to setting mode 2, you must push and hold the next page button
(BS1) for 5 seconds. (You cannot enter setting mode 2 while setting mode 1 is set.)
Setting Procedure
1. Push the SET button and match with the setting item (LED display). (All 10 settings)
2. Push the RETURN button (BS3) and the present settings flicker (LED display).
3. Push the SET button (BS2) and match with each setting (LED flicker display).
4. Push the RETURN button (BS3) and enter the settings.
5. Push the RETURN button (BS3) and return to the initial status.
Note:
1. If you become unsure of how to proceed, push the MODE button (BS1) and return to setting mode 1.
2. The initial status of setting mode 2 is the status of setting item No. 1 in mode 2.
Setting Items
64
Setting item
Description
1
EMG
Emergency
(Emergency
operation when
operation 1)
inverter type
outdoor unit
malfunctions.
2
Cool/heat
Address for
unified address
cool/heat
unified
operation
3
Low noise /
Address for
demand
low noise /
address
demand
operation.
4
Forced fan
Indoor unit fan
switch
turns while unit
is stopped.
5
Indoor unit
Allows operation of
forced
indoor unit from
operation
outdoor unit.
6
Frequency fix
Fixes compressor
frequency.
INV : (60Hz+OFF)
STD1: (ON+OFF)
STD2: (ON+OFF)
7
TE setting
Low pressure
setting for
cooling.
8
TC setting
High pressure
setting for
Note 1
heating
9
Defrost setting
Temperature
setting for
Note 1
defrost.
10
Air NET
Address for
address
Air NET
LED display
H1P H2P H3P H4P H5P H6P H7P
Emergency operation
(Operates by constant speed outdoor unit
only.)
Normal operation
Address
Binary number
(5 digits)
Address
Binary number
(5 digits)
Forced fan operation
(H tap)
Normal operation
Indoor unit forced
operation
Normal operation
Frequency fix
Normal operation
High
Normal (factory set)
Low
Quick defrost
Normal (factory set)
Slow defrost
Address
Binary number
(6 digits)
: http://splitoff.ru/tehn-doc.html
SiE33-003
LED display
H1P H2P H3P H4P H5P H6P H7P
0
1
2
31
0
1
2
31
0
1
2
63