Daikin VRV Plus Series General Information Manual page 40

R-407c
Hide thumbs Also See for VRV Plus Series:
Table of Contents

Advertisement

Si33-003.book Page 36 Monday, June 25, 2001 9:06 AM
Installation
3.2.8
Drain Pipe Work Indoor units
Drain Pipe Gradient
a) The drain pipe must be fitted at a gradient of at least 1/100.
and Support
b) Suspension bolts should be used to support long stretches of drain pipe in order to ensure that a
Spacing of supports for horizontal piping
c) The lenght of pipe laid horizontally should be kept to a minimum.
Drain Trap
Fit any indoor unit whose drain pipe connection is subjected to negative pressure, with a drain trap.
(FXYMP40~125 only)
a) Rig the drain trap as shown in the drawing bellow.
b) Provide one trap per unit. A single trap for converging units will prove ineffective.
c) Rig the trap to allow for future cleaning.
36
Operational steps
Install indoor unit
Connect drain pipe
The drain pipe should be as short as possible and free from airlocks.
gradient of 1/100 is maintained. (PVC pipes should not be bent)
Class
Nominal diameter
Rigid PVC pipe
25~40mm
Check for water
leaks
Spacing
1~1.5m
: http://splitoff.ru/tehn-doc.html
SiE33-003
Insulate drain pipe
(V0999)
General Information