Service Tools; Tool Compatibility - Daikin VRV Plus Series General Information Manual

R-407c
Hide thumbs Also See for VRV Plus Series:
Table of Contents

Advertisement

Si33-003.book Page 176 Monday, June 25, 2001 9:06 AM

Service Tools

5. Service Tools

R-407C is approximately 10% higher.
These refrigerants use ether oil for refrigerant oil instead of suniso oil. If oil of an incorrect type is
mixed in R410A and R-407C, sludge results in the refrigerants and causes equipment problems.
Therefore, gauge manifolds and charge hoses that are used with a previous refrigerant (R22)
cannnot be used for products that use new refrigerants.
Be sure to use dedicated tools and devices.
5.1

Tool Compatibility

The following chart shows tools that must be procured to use new refrigerants and conventional tools that
can be shared. (For details of individual tools, see the section from page177.)
176
: http://splitoff.ru/tehn-doc.html
New Refrigerant R-407C
SiE33-003