Technical specifications
12.1 General technical specifications
Type of condition
Atmospheric pressure
Relative humidity
Sinusoidal oscillations to
IEC 60068-2-6
Impact to IEC 60068-2-27
12.1.4

Mechanical and climatic ambient conditions for operation

Conditions of use
The described components are designed for use in a fixed, non-sheltered location. The
operating conditions exceed the requirements of IEC 61131 Part 2.
The described components meet the conditions of application of the class 4K4H according to
DIN EN 60721‑3‑4.
Use with additional measures
The described components must not be operated without additional measures:
● at locations with a high degree of ionizing radiation
● in aggressive environments caused, for example, by
– the development of dust
– corrosive vapors or gases
– strong electric or magnetic fields
● in installations requiring special monitoring, for example
– elevators
– electrical plants in potentially hazardous areas
An additional measure can be installation in a cabinet or in an enclosure, for instance.
Mechanical ambient conditions
The mechanical ambient conditions for the described components are specified in the table
below for sinusoidal vibrations.
Table 12-5
Frequency range in
Hz
5 ≤ f ≤ 8.4
8.4 ≤ f ≤ 150
134
Mechanical ambient conditions
Amplitude 3.5 mm
Constant acceleration 9.8 m/s
Permitted range
From 1080 hPa to 606 hPa
(corresponding to a height of ‑1000 m to 4000 m)
From 5% to 95%, non-condensing
5 - 8.4 Hz: 3.5 mm
8.4 - 500 Hz: 9.8 m/s
2
250 m/s
, 6 ms, 1000 shocks
2
2
Commissioning Manual, 07/2018, A5E39252870-AC