8.4.2

"Commissioning Wizard: Complete" dialog

You can find detailed information on the use of the wizard in the respective dialog window.
Table 8-2
"CFU ... Configuration" wizard
Step
Function in Commissioning Wizard: Complete
1
Specify I&M data of the CFU
● Display of article number, serial number, hardware version and firmware version of the CFU.
● Setting of I&M data of the CFU
● Only the installation date can be set for a BusAdapter.
2
Configure power supply and monitoring of electronics temperature
● Monitor redundant power supply
The CFU enables connection of 2 power supplies.
If the power supply is configured as "redundant", a diagnostic interrupt is triggered if one power supply
is missing.
● Monitor power supply faults
A diagnostic interrupt can be configured for short-term faults.
● Monitor electronics temperature of the CFU
Recommendation:
Configure the warning limits for the temperature message according to the installation situation.
In particular, in the case of installation in an enclosure and/or vertical installation.
The electronics temperature can be higher than the permissible ambient temperature of the CFU.
When the permissible electronics temperature is exceeded, an alarm is signaled.
3
Verify freely configurable channels (DIQ<n>)
● Display of the hardware parameters for the freely configurable channels (DIQ) transferred from HW Config.
4
Status of the automatic addressing on PROFIBUS PA
● Enabling and disabling of individual fieldbus connections.
● Status: Display for commissioning of field devices (automatic addressing, reading out of supported IOs)
● Display of an active service port. A configured service port is marked with "On".
SIMATIC CFU
Commissioning Manual, 07/2018, A5E39252870-AC
Commissioning
8.4 Configuring CFU with PDM
57