Climatic Ambient Conditions - Siemens SICAM A8000 Series Manual

Hide thumbs Also See for SICAM A8000 Series:
Table of Contents

Advertisement

Introduction
1.4

Climatic Ambient Conditions

Parameter
Minimum air temperature
(cold)
Maximum air temperature
(dry heat)
Maximum air temperature
for safe operation
Cyclic damp heat
Temperature gradient
Relative air humidity
Absolute air humidity
Air pressure
Temperature with storage
and transport
Pollution degree
1)
applies for horizontal mounting
2)
applies for vertical mounting (I/O Modules, Remote I/O interface)
3)
applies for vertical mounting in terms of personal and system safety
20
Value
-40°C/96 h
1)
70°C/96 h
2)
50°C/96 h
10% rH
2)
55°C
3)
25/40°C/120 h
95% rH
≤ 30°C/h
5...95%
≤ 35 g/m
3
70...106 kPa
(up to 3000 m)
-30...+85°C
2
Unrestricted
Test standard
Product standard Class
IEC 60068-2-1
IEC 60870-2-2
Ad
IEC 60654-1
IEC 60068-2-2
IEC 60870-2-2
Bd
IEC 60654-1
IEC 61010-1
IEC 60068-2-30
IEC 60870-2-2
IEC 60654-1
IEC 60870-2-2
IEC 60654-1
IEC 60870-2-2
IEC 60654-1
IEC 60870-2-2
IEC 60654-1
IEC 61010-1
SICAM A8000 Series, SICAM I/O Modules
DC8-012-2.06, Edition 09.2019
C2/C3
C2/C3
C3
C3
C2
C2
C1
C1
C2
C2
C2
C2

Hide quick links: