Commissioning
8.4 Configuring CFU with PDM
Step
Function in Commissioning Wizard: Complete
5
Configure type of field devices on PROFIBUS PA (FB<n>)
● Selection of how a connected PROFIBUS PA device is to behave:
- Profile (recommended)
- Manufacturer-specific device description
You can find additional information on this in section "Configuring a PROFIBUS PA field device (offline)
(Page 71)".
● Assigning/changing device name
● Information on field devices
● Select the desired field device profile in the "Change IO in ..." drop-down list.
● Lock/freeze function
Prevents unintentional changes to the configuration in the CFU.
● Display of an active service port:
Note: If a fieldbus connection is configured as a service port, the port designation changes from "FBx" to
"FBx --> FBy".
6
Configure extended diagnostic possibilities for PROFIBUS PA
Extended fieldbus diagnostics
● Voltage monitoring for the fieldbus connection (Min alarm)
Fixed low alarm limit for each fieldbus connection.
● Voltage monitoring for the fieldbus connection (Min warning)
User-defined warning limit for each fieldbus connection.
● Spur line current deviation (valid for all fieldbus connections):
Permissible percentage deviation from the set reference current value
● Reference current value
Set a reference current value corresponding to the technical specifications of the field device after
commissioning.
7
Commissioning overview
Shows the status of the connected components:
● Commissioning status
● Power supply X80/X81
● Freely configurable channels DIQ0 to DIQ7
● Fieldbus connections FB0 to FB7
8.4.3

"Commissioning Wizard: Add/remove/replace field devices only"

If you click the "Commissioning Wizard: Add/remove/replace field devices only" button, you
go directly to step 4/6 of the commissioning wizard.
Simplified commissioning of connected field devices
You can find information on this in section "Simplified commissioning of connected field
devices (Page 85)".
58
Commissioning Manual, 07/2018, A5E39252870-AC