The CFU is in data exchange mode with the IO Controller.
CFU PA: Activating PROFIsafe operation mode for field devices
If you want to connect field devices to the CFU PA that support PROFIsafe operation mode
(mode: S4), you must consider the following:
PROFIsafe operation mode may only be activated after commissioning of the field devices. In
the PROFIsafe mode S4, the field device prohibits changes of any kind.
● S4 = PROFIsafe operation mode
● S3 = Prepared for safe mode, check completed
● S2 = Prepared for safe mode, not checked
8.4

Configuring CFU with PDM

8.4.1

Using a wizard for CFU configuration

Using the "CFU PA ... Configuration" wizard
The CFU can be commissioned using the wizard.
Compared to commissioning of the CFU with STEP 7 alone, additional options and functions
are available in the CFU when commissioning with the wizard.
● You can find information about this in section ""Commissioning Wizard: Complete" dialog
(Page 57)".
Requirement
Online connection to the CFU
Opening the wizard
1. Select the CFU in the component view.
2. Select the shortcut menu command Edit > Start SIMATIC PDM.
SIMATIC PDM opens.
3. In SIMATIC PDM, select the menu command Device > CFU PA <Vx.x> Configuration.
The "CFU PA ... Configuration" dialog window opens.
You can find detailed information on the use of the wizard in its individual dialog windows.
SIMATIC CFU
Commissioning Manual, 07/2018, A5E39252870-AC
Commissioning
8.4 Configuring CFU with PDM
55