8.4.4

"Commissioning History" dialog

The history of changes made with the "CFU ... Configuration" wizard is shown in this dialog
box.
The memory is non-volatile.
8.4.5

"Diagnostic buffer" dialog

The history of all diagnostic interrupts is shown in this dialog window.
The memory is volatile.
8.4.6

"Expert Functions" dialog

You can do the following in this dialog window:
Button
Resetting over-tem‐
perature alarm
Reading out field de‐
vices data again
Restart the field de‐
vice
8.5

Preparing the CFU for commissioning

8.5.1

Rules for device names

A CFU must have a device name so that an IO controller can address the CFU as an IO device.
This approach was chosen for PROFINET because names are easier to understand than
complex IP addresses.
The device name must be unique in the PROFINET IO system.
The assignment of a device name for the CFU corresponds to the setting of the PROFIBUS
address for a DP slave.
Rules for specifying the device name (in accordance with IEC 61158-6-10)
● A device name may have a maximum length of 240 characters (letters, numbers, hyphen
or dot).
● A device name must consist of at least one character.
SIMATIC CFU
Commissioning Manual, 07/2018, A5E39252870-AC
Function
Reset a thermal overload of the freely configurable channels (DIQ reset)
CFU PA:
Read out all supported IOs of a PROFIBUS PA device again
CFU PA:
The power supply to the field device is temporarily switched off and on again.
Subsequently, the automatic addressing is triggered and all supported IOs of a
PROFIBUS PA device are read out again
8.5 Preparing the CFU for commissioning
Commissioning
59