Siemens SIMATIC ET 200pro Quick Manual page 231

Motor starters
Hide thumbs Also See for SIMATIC ET 200pro:
Table of Contents

Advertisement

ID no. Byte
Signaling bit
4
1444
22
Manual operation local –
input controls
5
1445
22
Manual local operation – con-
trol device controls
6
1446
22
Manual local operation – PC
controls
Parameters
0
364
8
Parameterization active
1
365
8
Incorrect parameter value
2
366
8
Parameter change illegal in
the ON state
3
368
8
Parameter block CPU / Mas-
ter ON
4
384
8
No external start-up parame-
ters received
5
8
Reserved = 0
6
371
8
Memory module defective
7
370
8
Memory module not plugged
Device function
0
379
9
Self-test active
1
380
9
Self-test OK
2
381
9
Error in self-test
3
369
9
Factory setting
restored
4...5
9
Memory module
372
373
374
Table D-10: Data record 92 – read device diagnosis (Continued)
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
1)
F no.
2)
F16
(F24)
F26
(F24)
F9
Data formats and data records
Meaning / Acknowledgment
Manual operating mode – local active,
+ input controls active
Not supported
Manual operating mode – local active,
+ PC controls active
Signaling bit is continuously updated
Signaling bit is always deleted if acknowl-
edged with trip reset or valid parameter
received.
Leads to tripping on start-up
Attempted parameter change with motor run-
ning or device function concerned that caused
tripping.
Signaling bit is always deleted if acknowl-
edged with trip reset or valid parameter
received.
Signaling bit is continuously updated
Motor starter ignores parameters from the
PLC
Signaling bit is always deleted on change
from start-up to normal operating mode
Signaling bit is always deleted if acknowl-
edged with trip reset.
Leads to tripping on start-up
Signaling bit is continuously updated
Signaling bit is continuously updated
Signaling bit is continuously updated
Signaling bit can only be deleted by switch-
ing the supply voltage (DC 24 V-NS) off / on
when the error cause has been removed.
Signaling bit is always deleted if acknowl-
edged with 'trip reset'.
00 : not used (state after power on)
01 : programming active
10 : programming successful
11 : Programming defective F26,
(F24 only for start-up)
Signaling bit is always deleted when
acknowledged with trip reset.
D-19