Siemens SIMATIC ET 200pro Quick Manual page 103

Motor starters
Hide thumbs Also See for SIMATIC ET 200pro:
Table of Contents

Advertisement

Parameters
Blocking current limit value
Blocking time limit value
Type of start-up
Type of run-down
Current limit
Startup time
Run-down time
Start voltage
Stop voltage
Response to CPU / Master
STOP
General warning diagnosis
Group diagnosis
1)
Digital inputs
Signal
Level
Signal delay
Signal extension
Action
only make contact
only make contact
only make contact
only make contact
3)
400 V brake output
Brake release delay
Hold time on stopping
1)
only for high feature motor starters
2)
of the rated operating current
3)
order option
Table 8-2:
Parameters for motor starters DSe, RSe (standard and high feature); sDSSte / sDSte, sRSSte / sRSte
(cont.)
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
Action,
value range
1)
150% ... 1000% I
with soft starter only 800%
1)
1 s ... 5 s
direct
Voltage ramp
Current limitation
Voltage ramp and current limita-
tion
free run-down
Voltage ramp
0.15 A - 9 A
9 A - 12 A
0 s ... 120 s
0 s ... 120 s
4 ... 20
4 ... 18
Switch substitute value
Retain the last value
1)
Disable
Enable
Disable
Enable
4 inputs
Latching
Not latching
Break contact
Make contact
10 ms ... 80 ms
0 s ... 200 ms
No action
Trip without restart
Trip with restart
Tripping end position clockwise
Tripping end position counter-
clockwise
General warning
Operating mode 'Manual opera-
tion local'
Emergency start
Motor CLOCKWISE
Motor COUNTER-CLOCKWISE
Quick stop
Trip reset
–2.5 s ... 2.5 s
0 s ... 25 s
Factory setting
,
800%
e
1 s
Voltage ramp and
current limitation
free run-down
0 - 600 %
600%
0 - 550 %
20 s
0 s
8
8
Switch substitute
value
Enabled
Disable
Not latching
Make contact
10 ms
0 s
No action
0 s
0 s
Applica-
bility
Module
Module
Module
Module
Module
Module
Module
Module
Module
8-11