Product Information
Caution
Before installing and commissioning, please read carefully the safety
instructions and warnings of the Operating Instructions and follow the
warning labels attached to the equipment. Make sure that the warning
labels are kept in a legible condition and replace missing or damaged
labels.
Warning
This equipment contains dangerous voltages and controls potentially
dangerous rotating mechanical parts. Non-compliance with the
warnings or failure to follow the instructions contained in the manual
can result in loss of life, severe personal injury or serious damage to
property.
Protection in case of direct contact by means of SELV / PELV is only
permissible in areas with equipotential bonding and in dry indoor
rooms. If these conditions are not fulfilled, other protective measures
against electric shock must be applied e.g. protective insulation.
Only suitably qualified personnel should work on this equipment, and
only after becoming familiar with all safety notices, installation,
operation and maintenance procedures contained in the operating
instruction manual. The successful and safe operation of this
equipment is dependent upon its proper handling, installation,
operation and maintenance.
The power supply, DC and motor terminals, the brake and thermistor
cables can carry dangerous voltages even if the inverter is inoperative.
Wait at least five minutes to allow the unit to discharge after switching
off the line supply before carrying out any installation work.
When connecting the line supply to the Inverter, make sure that the
terminal case of the motor is closed.
If any LED is extinguished this does not indicate that the device is
unplugged from the mains and is in idle state.
The inverter must always be grounded.
Isolate the line supply before making or changing connections to the
unit.
Ensure that the inverter is configured for the correct supply voltage.
The inverter must not be connected to a higher voltage supply.
 Siemens AG 2009
SIMATIC ET200pro FC
6SL3235-0TE21-1RB0
6SL3235-0TE21-1SB0
1 / 2
A5E01490807A4
SIMATIC ET200pro FC
Supplement to Operating Instructions A5E01100763B AA, Edition 11/2007
General
ET200pro stations with Frequency converters must be wall-mounted in horizontal
orientation as shown in the figure. ET200pro stations without Frequency converters can
be mounted in any orientation.
The temperature sensor and brake module connections are at DC link negative
potential. Appropriate precautions against touching these connections and appropriate
insulation on the cables must be used.
Cables that are not used should be individually insulated and not earthed.
It is strictly prohibited to disconnect the cable between inverter and motor. Any
disconnection of the mains must be performed on the mains-side of the Inverter.
Under no circumstances shall any kind of switch or contactor be placed in the circuits
between the Inverter and the motor. For maintenance, ensure that the motor cable is
unplugged at the Inverter.
Section 4.9
Only the following modules are allowed to be connected between the F-RSM or F-
Switch and the fail-safe frequency converter (ET200pro FC Fail-safe):
direct or reversing starters
ET200pro FC Standard
ET200pro FC Fail-safe
The 400 V shutdown module must not be connected between the F-RSM or F-
Switch and the fail-safe frequency converter (ET200pro FC Fail-safe)!
A5E01490807A4
Product Information
6SL3235-0TE21-1RB0
6SL3235-0TE21-1SB0
*A5E01490807A4*
2 / 2
Printed in the United Kingdom
Subject to change without prior notice

Advertisement

loading

Summary of Contents for Siemens SIMATIC ET200pro FC Series

  • Page 1 Switch and the fail-safe frequency converter (ET200pro FC Fail-safe)! • Ensure that the inverter is configured for the correct supply voltage. The inverter must not be connected to a higher voltage supply. *A5E01490807A4*  Siemens AG 2009 1 / 2 A5E01490807A4 A5E01490807A4 2 / 2...
  • Page 2 • Stellen Sie sicher, dass der Umrichter an die Versorgungsspannung *A5E01490807A4* angeschlossen wird, für die er ausgelegt ist. Er darf nicht an eine zu hohe Versorgungsspannung angeschlossen werden.  Siemens AG 2009 1 / 2 A5E01490807A4 A5E01490807A4 2 / 2...

This manual is also suitable for:

Simatic et200pro fc 6sl3235-0te21-1rb0Simatic et200pro fc 6sl3235-0te21-1sb0