Siemens SIMATIC ET 200pro Quick Manual page 116

Motor starters
Hide thumbs Also See for SIMATIC ET 200pro:
Table of Contents

Advertisement

Stop voltage
The parameter "stop voltage" sets the voltage value whereby run-down type
"voltage ramp" aborts the run-down, i.e. is switched off.
Current limitation value
The parameter "current limitation value" limits the start-up current to the param-
eterized value.
Duty cycle
The relative duty cycle in % is the ratio between the load duration and cycle
time for consumer units that are frequently switched off and on.
The duty cycle can be calculates according to the following formula:
Formula key:
• Duty cycle [%]
• t
s
• t
b
• t
p
The following graphic shows the operation.
I
e
t
s
Figure 8-13: Duty cycle
Switching frequency
To prevent a thermal capacity overload of the devices, the maximum permitted
switching frequency must be adhered to without fail. To this end, the parameter
"Response to overload – thermal motor model" must be deactivated (deactiva-
tion without restart). Furthermore, the idle time for the cooling down character-
istics of the thermal motor model must be disabled in the default setting = 0
(see
Chapter 8.2.7
The following tables provide an overview of the switching frequencies / hour
according to the influencing factors.
8-24
t
ED
=
------------------------
t
+
s
start time [s]
operation time [s]
idle time [s]
t
t
b
p
Parameters for idle time).
+
t
s
b
t
+
t
b
p
t
SIMATIC - ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04