Data formats and data records
ID no. Byte
Signaling bit
3
312
1
Start-up active
4
313
1
Coasting down active
5
315
1
Brake output active
6
316
1
Electrical braking active
7
314
1
Creep feed active
1
1470
19
Ready to start for Motor ON
2
1414
19
Switching element short-cir-
cuited
Protective function: Motor / Cable / Short circuit
0
324
2
Temperature sensor overload F 4
1
325
2
Temperature sensor wire
break
2
326
2
Temperature sensor short cir-
cuit
3
327
2
Thermal motor model over-
load
4
328
2
Overload tripping
5
329
2
Idle time active
6
330
2
Cooling time active
7
305
2
Fail-safe tripping
0
331
3
Line protection overload
1
332
3
Line protection tripping
2
333
3
Circuit breaker tripped
3
320
3
Current limitation active
4
321
3
Target value = actual value
5
323
3
Intermediate circuit voltage
too high
Table D-10: Data record 92 – read device diagnosis (Continued)
D-16
1)
F no.
Meaning / Acknowledgment
In the case of soft starters
Signaling bit is continuously updated
Brake output is switched on by user
Signaling bit is continuously updated
Brake output is switched on by motor starter
Signaling bit is continuously updated
Signaling bit is continuously updated
Device ready to operate, switch-on is possible
E.g. contactor fused
Overload detected
Signaling bit is continuously updated
F6
Thermistor circuit interrupted
Signaling bit is continuously updated
F1
Short circuit in thermistor circuit
Signaling bit is continuously updated
F4
Overload detected
Signaling bit is continuously updated
F24
Overload detected and tripping
Signaling bit is deleted when cause of the
trip has been removed and acknowledged
with trip reset / autoreset
Signaling bit is continuously updated
Signaling bit is continuously updated
F25
Tripped
F4
Cable between motor starter and motor over-
loaded
Signaling bit is continuously updated
F24
Cable between motor starter and motor over-
load and tripping
Signaling bit is deleted when cause of the trip
is removed and acknowledged with trip reset
F1,
Signaling bit is deleted if acknowledged with
F24
"Trip reset" and cause of the trip has been
removed.
Motor current is limited to parameterized
value. Signaling bit is continuously updated
Target frequency speed adjuster = actual fre-
quency. Signaling bit is continuously updated
Speed adjuster
Signaling bit is continuously updated
SIMATIC - ET 200pro motor starter