Siemens SIMATIC ET 200pro Quick Manual page 163

Motor starters
Hide thumbs Also See for SIMATIC ET 200pro:
Table of Contents

Advertisement

Input n – action
– level – Signal
Motor CLOCK-
S / –
WISE
Motor COUNTER-
S / –
CLOCKWISE
Quick stop
NO /
NC
Trip reset
S / –
Key:
NO: Make contact
la: latching
Table 10-13: Description of 'Input n – action' (cont.)
SIMATIC – ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
Operati
ng
mode
n.la / la
Manual
• For these operations, the motor starter must be
opera-
in the operating mode 'Manual operation local'.
tion
• The device braking parameters are evaluated.
local
• Motor CLOCKWISE: Switch the motor and brake
output on and off together (clockwise).
• Motor COUNTER-CLOCKWISE: Switch the motor
n.la / la
Manual
and brake output on and off together (counter-
opera-
clockwise).
tion
• Only permitted as a make contact!
local
la: The input action is triggered as long as the
n.la / la
all
• Motor and brake output are switched off without
general faults.
• 'Quick-Stop' has priority over
'Motor CLOCKWISE' and 'Motor COUNTER-
CLOCKWISE'
la: The input action responds to the active edge of
n.la / –
all
• 'Trip reset' is triggered once
NC: break contact (normally closed)
n.la:
Description
active level of the input signal is present.
The input trigger is deleted by the input action
"quick stop" or "general fault".
the input signal. This also enables deactivation
if the input signal is active.
The input trigger is deleted by
- Deleting the control commands/input actions
'Motor CLOCKWISE' and 'Motor COUNTER-
CLOCKWISE'
not latching
Activation and deactivation of the input action
depends on the status of the input signal
(=inching mode)
10-23

Advertisement

Table of Contents
loading