Permitted switching frequency
Insulation resistance
Rated impulse strength U
Rated insulation voltage U
Protective separation between main and control current
circuits
Circuits with rated voltage U
ground
• 0 V <U
< 50 V
e
• 300V<U
< 600V
e
Short-circuit protection
Rated operating current
Rated limit short circuit-breaking capacity I
Table 8-3: Technical data of the motor starters (cont.)
Note
This is a product for environment A (industrial sector). In household environ-
ments, this device can cause unwanted radio interference. In this case, the user
can be obliged to institute appropriate measures.
8-14
imp
i
against other circuits or
e
CU
max. 80/h
6 kV
400 V
400 V, in accordance with EN 60947-1
Appendix N
testing voltage
complying with IEC 61131, Part 2
DC 500 V
DC 2.6 kV to ground
16 A
100 kA at 400 V
SIMATIC - ET 200pro motor starter
GWA 4NEB 950 5661-02 DS 04
see
Table 8-6
to
Table 8-7
4 kV