Parts of the H-S81-HS System
Threshold Setting
The following parameters can be set for each module through the configuration program or directly
on the control panel in the operator cycle, access level 3:
•
Pre-alarm threshold.
•
Alarm threshold.
•
Current value below which a trouble condition is signaled
•
Calibration mixture concentration value for end of scale calibration
Zero Point Calibration
Calibrate the zero point as reported below:
•
Disable the channel of the module to be calibrated from the operator cycle.
•
Enter the diagnosis cycle of the module to be calibrated.
•
Disconnect the channel to be calibrated (1-8).
•
Make sure that no gas is present near the sensor to be calibrated.
•
Press the "1" key to calibrate the zero point of the channel.
•
The new zero value is stored in the memory of the module.
•
Press "0" to cancel the operation for the channel.
•
Exit the module diagnosis cycle and enable the channel.
NOTE: The zero point can be calibrated only with zero values ranging between 3 and 5mA.
End of Scale Calibration
Calibrate the end of scale as follows:
•
Disable the channel of the module to be calibrated from the operator cycle.
•
Enter the diagnosis cycle of the module to be calibrated.
•
Disconnect the channel to be calibrated (1-8).
•
Apply gas to the sensor according to the percentage set during configuration.
•
Wait for the gas value measured by the module to stabilize.
•
Press the key "3" to calibrate the end of scale for the channel.
•
Press "2" to cancel the operation for the channel.
•
Exit the module diagnosis cycle and enable the channel.
NOTE: The end of scale can be calibrated only if the current value measured by the module is
±3mA than the set calibration value.
Field Connections
The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.