General Features

1.3 General Features
• Serial communication interface:
• Ethernet communication interface:
• Maximum number of programmable zones:
• Maximum number of programmable points per zone: 99 inputs 99 outputs 99 links
• Exportable local variables via network:
• Importable remote variables via network:
• System variables (Local):
• Maximum number of modules:
• Time slots with holiday management:
• CPU redundancy:
• I/O bus redundancy:
• Module redundancy:
• Hot swap capability:
• Centralization between control panels:
• Supervisory system:
• Management of time slots:
• Default outputs:
• Default inputs:
• Available protocols:
NOTE:
detectors and/or fire alarm buttons can be set in each zone of the area-1.
1.3.1 Mechanical Properties
H-S81-HS/1R
• Steelwork type
• Color
• Protection class
• Type of installation
• Dimensions
H-S81-HS/2R
• Steelwork type
• Color
• Protection class
• Type of installation
• Dimensions
H-S81-HS/1-10R
• Steelwork type:
• Color:
• Protection class:
• Type of installation: Floor ground installation
• Dimensions:
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
In order to comply with the requirements of EN54-2 standard, a maximum of 32
Metal, with transparent door and revolving inner door
RAL 7035
IP30
Wall installation
H=700mm W=600mm D=400mm
Metal, with transparent door and revolving inner door
RAL 7035
IP30
Wall installation
H=1100mm W=600mm D=400mm
Metal, with transparent door and revolving inner door
RAL 7032
IP30
H=2100mm W=800mm D=800mm
2 x RS232
10/100BaseT with RJ45 connector
300 fire alarm zones + 300 burglar alarm zones
Max. 250
Max. 999
64
130 (10 rack version)
10 (with 10 intervals each)
Optional
Optional
Optional only for safety related modules
Available for all modules
Via LAN network with RCP protocol
Max. three supervisors per control panel
10 categories with management of holidays
16 SPDT contacts
10 opto-isolated inputs
MODBUS RTU
General Description