Power Supply Set
Open collector replications
RS 232
2.1.6 PU-A0008-1 Power Supply Module
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Tag
Terminal
Name
M1
PSU1-Fault
M2
PSU2-Fault
M3
Fault
M4
Battery status
M5
Charge Status
8
M6
Rip.1
M7
Rip.2
M8
GND
M9
+S
M10
-S
Tag
Pin
Name
1
N.C.
2
Txd
3
Rxd
4
N.C.
9
5
GND
6
N.C.
7
N.C.
8
N.C.
9
N.C.

Description

It is a switching power supply unit with universal input able to pro-
vide a maximum current of 20A at 25VDC. It is placed in a 19 inch
rack slot and used in combination with the PU-A0009-1 battery char-
ger in compliance with EN54-4 standard. The power supply unit fea-
tures a circuit for load distribution which allows the parallel
connection of multiple power supply units, up to a maximum of four
units. Module hot swapping is allowed (Hot Plug). On the front panel
there are: two green LEDs signaling the proper presence of input and
output voltage; a yellow LED that lights up in case of failure; and a
button for shutting the module down before hot-swapping.
Parts of the H-S81-HS System
Function
Primary power supply failure
Secondary power supply failure
Internal failure
Battery status (charge/supply)
Battery charge status (full charge/trickle charge)
Programmable output
Programmable output
External temperature probe display
External temperature probe positive
External temperature probe negative
Function
Not used
RS232 data transmission
RS232 data reception
Not used
RS232 common
Not used
Not used
Not used
Not used
35