Common Communication Link
Fiber-Optic and Twisted Pair Wiring between Multiple Panels
A mixture of fiber-optic cable and twisted-pair wiring between multiple panels is shown in Figure 5.9. Class X cabling is shown with a dot-
ted line.

5.5 Setting the ID for Each Panel

NOTE: It is important that much thought is given when choosing the IDs for each panel. It is difficult to change the IDs once panel
programming has begun.
Use the DIP switch positions 1 through 5 to set the ID for each panel. Note that switches 7 and 8 are not used and should remain in the OFF
position. See the figure below for possible DIP switch settings. Address 0 is an invalid address and cannot be used.
ON
OFF
1
2 3
4 5 6
56
last control panel/SK-NIC
next control panel/SK-NIC
first control panel/SK-NIC
Figure 5.9 Twisted-Pair and Fiber-Optic Combination Wiring Example
Address
7 8
1
2 3
4 5 6
0
1
2
3
4
Figure 5.10 Panel ID Settings
TB2
A
B
A
port 2
B
in
port 1
out
TB2
A
B
A
port 2
B
in
port 1
out
in
port 2
out
in
port 1
out
Address
7 8
1
2 3
4 5 6
5
6
7
8
9
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Setting the ID for Each Panel
Class X
wiring
Address
7 8
1
2 3
4 5 6
10
11
12
13
Address
7 8
14
15
16
17