6.2.4 Light Indicators
Each extinguishing zone shall be provided with a S81-F6001-1 module that gathers all the main
indications relating to a single extinguishing zone. The front panel of said module shall include
eight LED indicators signaling the following statuses:
Function
"Activated" condition
"Released" condition
Fault condition
Out of service condition
Emergency shutdown
Emergency hold
Only manual mode
Reserve bank selection
Monitoring of part status
1 This option can be used as an alternative to an optional function.
Detailed information concerning alarm, trouble and out of service conditions are shown on the con-
trol panel display.
6.2.5 Monitored Inputs
Use S81-F3002 modules for controlling the following devices:
Inputs for manual actuation devices (manual discharge buttons)
Inputs for devices indicating extinguishing agent flow, such as pressure switches or flow
switches (PSH)
Inputs for devices monitoring part status (valve position or weight monitoring devices)
Inputs for discharge sequence extension (HOLD)
Inputs for devices allowing to switch from Manual/Automatic to Manual only operation
Inputs for devices allowing to select MAIN/RESERVE
NOTE: A maximum of 5 manual discharge buttons and a maximum of 5 Emergency Hold
devices can be connected per fire extinguishing zone.
6.2.6 Monitored Outputs
Use S81-F5001, S81-F5004 modules for monitoring and controlling the following devices:
Releasing device control outputs (solenoids, deluge valves, etc.)
Outputs for controlling equipment inside the system (pilot cylinders, etc.)
Use S81-F5003 modules for monitoring and controlling the following devices:
Outputs for visual and audible alarm device control (TOA)
6.2.7 Non-monitored Outputs
S81-F5002 type modules, combined with the termination module S81-T8007, can monitor the out-
puts controlling equipment external to the system (door release, ventilation stop, etc.)
122
Notes for the Development of Systems in Compliance with the EN12094-1 Standard
Color
Red
Red
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
1
Yellow
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Label
Notes
Activated
Compulsory
Released
Compulsory
Fault
Compulsory
Disabled
Compulsory
Inhibit
Optional
Hold
Optional
Automatic-Off
Optional
Reserve bank
Optional
Optional