3: S81-F4002-1 & S81-F4002-2; Description; Technical Features; Status Indications - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

I/O modules
2.4.3 S81-F4002-1 & S81-F4002-2

Status Indications

Module front panel includes three LEDs and a three-digit display for each channel.
Input channel status
Normal
Disabled
Trouble
Pre-alarm
Alarm
Key to symbols: ⊗= steady on LED; − = LED off; ∅= flashing LED

Three-Digit Display

The three-digit display generally shows the measured value in the programmed format. Moreover,
it shows some fault codes according to the following table.
No.
---
F00
F01
F02
F03
Fx.x
E00
+/-999
1 For current values lower than the set trouble threshold and exceeding 1mA, the display
will show the value of the measured current in mA preceded by letter F. Please refer to
the manual of the connected device for identifying the type of anomaly.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015

Description

Safety related module with 2 x 4-20mA analog inputs and two thresholds to be
programmed on the module through the operator cycle. The following transducer
types can be connected to this module: Explosion Sensors, Air Quality Sensors,
Oxygen Sensors, Temperature Sensors, 4-20mA General Sensors. The channel is
continuously tested during operation. The module features 4-20mA outputs that
provide the current value measured on the input. The analog value of each chan-
nel can be transferred to a DCS by means of the S81-F7006-1 Modbus RTU
module. This module can be duplicated for fault tolerant systems; in this case,
the two modules shall be placed on two adjacent racks in the same position. In
this configuration, the two detection lines are connected to both modules.

Technical Features

• Safety rating:
• Redundancy:
• Alarm threshold:
• Channel test:
• Measuring range
• Line short circuit condition:
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:
Channel Status
Initialization stage
Module/channel not configured
Line opening (current <1mA)
Over current (current >23.5mA)
Internal test failed
1
Device trouble
Memory data error CRC
Measured value
applicable up to SIL3
S81-F4002-2 model
2 programmable
continuously tested
0-24mA
with current >23.5mA
22-29VDC
60mA
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
yes
2nd Level
1st Level
Red LED
Red LED
Parts of the H-S81-HS System
Fault/Disabled
Yellow LED
¬
53