Technical Features; Description - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

Parts of the H-S81-HS System
58000-400MAR
Discovery Marine Heat detector
58000-700MAR
Discovery Marine Multi-sensor detector
58100-940MAR
Discovery Marine Manual Call Point
58100-975MAR
Discovery Marine W.P. Manual Call Point
58000-600
Discovery Optical smoke detector
58000-500
Discovery Ionization smoke detector
58000-700
Discovery Multi-sensor detector
58000-300
Discovery Carbon Monoxide detector
58000-305
Discovery Heat/Carbon Monoxide multi-sensor
58000-400
Discovery Heat detector
58100-908
Discovery Manual call Point Red
58100-950
Discovery W.P. Manual call Point Red
45681-393
Discovery Sounder/Beacon Base
58000-005
Discovery Open Area Sounder/Beacon
55000-295
Intelligent Dual IR Flame detector ATEX
55000-021
Intelligent Triple IR Flame detector ATEX
2.4.14 S81-F7010-1
Status Indications
The front panel includes 8 LEDs with the following functions:
LED
Active (Red LED)
Disabled (Yellow LED)
Fault (Yellow LED)
Loop Fault (Yellow LED)
Log on Fault (Yellow LED) Flashing in case of difference between the detected devices and the programmed ones.
Service (Yellow LED)
TX Pol. (Green LED)
RX Pol. (Green LED)
82

Description

Control module for addressable devices using System Sensor protocol. This
module can control up to a maximum of 188 fire detection modules including:
smoke, heat, combined detectors, alarm buttons, control modules, visual and
audible alarm devices.

Technical Features

• Redundancy:
• Operating modes:
• Number of devices per loop: 99 modules & 99 sensors
• Loop maximum current:
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:
Indication
Steady on if an input is under alarmed/activated condition
Steady on if an input or an output is disabled
Flashing in case of Fault condition
Flashing in case of loop short circuit or open loop
Flashing in case of in case of smoke detectors with dirty lenses
It lights up every time data are transmitted from the module to loop devices.
It lights up every time data from loop devices are received
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
D-HD
Powered by the loop
D-HSM
Powered by the loop
D-MCP
Powered by the loop
D-MCP
Powered by the loop
D-OSD
Powered by the loop
D-ISD
Powered by the loop
D-HSM
Powered by the loop
D-CMD
Powered by the loop
D-HCM
Powered by the loop
D-HD
Powered by the loop
D-MCP
Powered by the loop
D-MCP
Powered by the loop
D-SBB
Powered by the loop
D-ASB
Powered by the loop
X-FD
Powered by the loop
X-FD
Powered by the loop
No
Configuration via software.
500mA
22-29VDC
39mA
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
yes
I/O modules