Configuration; Field Connection - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

I/O modules

Configuration

By using the configuration program ProS81, the following parameters can be set for each input
channel:
Function
Operating mode:
Alarm verification function
Pre-alarm threshold
Alarm threshold
Channel status with line short circuit
Type of indication
Automatic alarm reset
Enable/Disable channel status export to Hosts
Enable/Disable commands from Hosts on the channel No, TCP1, TCP2, RS232

Field Connection

The module can be connected to field terminal block by using a flat or a multi-conductor cable,
depending on the used bus type.
S81-E2001-1 Bus
The module is connected to the S81-T8001-1 termination module with 16
terminals by using a 20-way flat cable.
S81-E2001-2 Bus
The module is connected to the field terminal block by the S81-CCT6 16-
conductor multi-polar cable. For S81-F3002-2 module redundant connec-
tion, use the S81-CCT1R cable.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Allowed values in SAFETY mode
Latching-NO, Latching-NC, Non-Latching-NO,
Non-Latching-NC,
Yes/No
10-250
10-250
Trouble / Alarm
Fire, Supervisory, Gas, Trouble, Hidden,
Buzzer Only
Yes/No
No, TCP1, TCP2, RS232
Parts of the H-S81-HS System
Allowed values in
SECURITY mode
Latching-NC
Disabled
Fixed threshold
Fixed threshold
Tampering
Burglar Alarm, Hidden
N0
No, TCP1, TCP2, RS232
No, TCP1, TCP2, RS232
47