2: Electrical Characteristics; 3: Reference Standards; 4: Climatic Conditions; 5: Mechanical Conditions - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

General Description
1.3.2 Electrical Characteristics
• Supply voltage
• Nominal frequency of the power supply
• Power supply set output voltage
1.3.3 Reference Standards
The H-S81-HS system was developed complying with the requirements of the following European
standards:
Reference standard
EN-54-2:1997 / A1:2006
EN-54-4: 1997 / A1:2002 / A2:2006
EN-12094-1:2003
EN-60950-1:2001
CEI 79-2:1998 + Ab2000
1.3.4 Climatic Conditions
The table below summarizes the climatic conditions for H-S81-HS system operation and storage.
The climatic conditions refer to the whole system.
NOTE: The operating temperature inside an electronic device significantly affects the duration of
its useful life. High operating temperatures and sharp temperature increases will significantly
reduce electronic device life. It is extremely important that the environmental operating conditions
are within the allowed ranges.
WARNING: REMOVE BATTERIES
!
SHOULD STORAGE TEMPERATURE BE LOWER THAN -30°C OR EXCEED +60°C, REMOVE
THE LITHIUM BATTERY ON CENTRAL UNITS (S81-U1002-1 MODULES).
1.3.5 Mechanical Conditions
The table below summarizes the type of mechanical tests undergone by the H-S81-HS system.
Standard
IEC 68-2-6
IEC 817
18
Description
Fire detection and fire alarm systems
Part 2: Control and indicating equipment
Fire detection and fire alarm systems
Part 4: Power supply equipment
Fixed firefighting systems. Components for gas extinguishing systems.
Requirements and test methods for electrical automatic control and delay devices
Information technology equipment – Safety - part 1:
General requirements
Intruder, burglar, hold up and anti-attack alarm systems. Particular requirements
for apparatus.
Parameter
Allowed range
Operating temperature
-5 - 50°C
Storage temperature
-40 - 85°C
Operating humidity
5 - 95% RH
Storage humidity
5 - 95% RH
Test
Vibration sinusoidal test (endurance)
Impact test
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
110-240 V~ (-15% + 10%)
50-60Hz
25VDC ±2%
Notes
Non-condensing
Non-condensing
Test Levels
Frequency range: 10-150Hz
Acceleration amplitude: 0.5g
Number of axis: 3
Number of sweep cycles: 20 per axis
Impact energy: 0.5J
Number of impact per point: 3
General Features