Technical Features; Description - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

I/O modules
Supported Devices
This module can control the following types of addressable devices:
Part Number

Description

S81-Mod-DI
Module with 8 non monitored inputs
S81-Mod-AIT
Module with 4 monitored inputs
S81-Mod-AI020
Module with 1 x 4-20 mA input
S81-Mod-AV010 Module with 1 x 0-10V input
S81-Mod-DO
Module with 8 open collector outputs
S81-Mod-DISP
255 message display module
1 A maximum of 64 modules can be installed in a loop.
2.4.13 S81-F7009-1
Status Indications
The front panel includes 8 LEDs with the following functions:
LED
Active (Red LED)
Disabled (Yellow LED)
Fault (Yellow LED)
Loop Fault (Yellow LED)
Log on Fault (Yellow LED)
Service (Yellow LED)
TX Pol. (Green LED)
RX Pol. (Green LED)
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Description
Control module for addressable devices using XP95/Discovery Apollo protocol.
This module can control up to a maximum of 127 fire detection modules includ-
ing: smoke, heat, combined detectors, alarm buttons, control modules, visual
and audible alarm devices.

Technical Features

• Redundancy:
• Number of devices per loop:
• Loop maximum current:
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:
Indication
Steady on if an input is under alarmed/activated condition
Steady on if an input or an output is disabled
Flashing in case of Fault condition
Flashing in case of loop short circuit or open loop
Flashing in case of difference between the detected devices and the programmed ones.
Flashing in case of in case of smoke detectors with dirty lenses
It lights up every time data are transmitted from the module to loop devices.
It lights up every time data from loop devices are received
Type Pros-81 Notes
DI
Requires external power supply
AIT
Requires external power supply
AI020
Requires external power supply
AV010
Requires external power supply
DO
Requires external power supply
DISP
Requires external power supply
No
127
400mA
22-29VDC
90mA
-5 - 50 °C
-30 - 80 °C
95% (RH) non-condensing
yes
Parts of the H-S81-HS System
1
79

Hide quick links:

Advertisement

Table of Contents
loading