I/O modules
2.4.2 S81-F4001-1 & S81-F4001-2

Status Indications

Module front panel includes three LEDs, a graphic LED bar, and a three-digit display.
Input channel status
Normal
Disabled
Trouble
Pre-alarm
Alarm
Key to symbols: ⊗= steady on LED; − = LED off; ∅= flashing LED
LED Bar
It indicates the 0-100% percentage of the measured value.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Figure 2.20 Standard Connection Diagram for Burglar Alarm

Description

Safety related module with 1 x 4-20mA analog input and two programmable
thresholds. It can control the following transducer types: explosion sensors, air
quality sensors, oxygen sensors, temperature sensors, 4-20mA general sensors.
The channel is continuously tested during operation. The module features a 4-
20mA output that provides the current value measured on the input. This analog
value can be transferred to a DCS by means of the S81-F7006-1 Modbus RTU
module. This module can be duplicated in fault tolerant systems; in this case, the
two modules shall be placed on two adjacent racks in the same position. In this
configuration, the detection lines is connected to both modules.

Technical Features

• Safety rating:
• Redundancy:
• Alarm threshold:
• Channel test:
• Measuring range
• Line short circuit condition:
• Supply voltage:
• Quiescent current:
• Operating temperature:
• Storage temperature:
• Maximum humidity:
• Hot swap capability:
applicable up to SIL3
S81-F4001-2 model
2 programmable thresholds
continuously tested
0-24mA
with current >23.5mA
22-29VDC
35mA
-5 - 50°C
-30 - 80°C
95% (RH) non-condensing
yes
2nd Level
1st Level
Red LED
Red LED
Parts of the H-S81-HS System
Fault/Disabled
Yellow LED
¬
49